Guest user

Products

Transducers

List of Transducers Contents
Active and Reactive Power Transducer
Voltage Transducer
Current Transducer
Resistor (Tap Position) Transducer
MPR-G3

Active and Reactive Power Transducer

Input-Output

Nom. Input Voltage (ph. to ph.)(Vn) 100V, 110V, 120V
Nominal Input Current (In) 1A, 5A
Output Current Range (Iomin-Iomax) 0-1, 5, 10,20mA, 4-20mA, -2.5 to +2.5 mA
Rated Frequency 45Hz - 55Hz (50Hz for Reactive Power Transducer)
Overload Continues (Voltage) 1.2Vn
Overload for 10 Seconds (Voltage) 1.5Vn
Overload Continues (Current) 1.5In
Overload for 1 Seconds (Current) 20In
Power Consumption <5VA
Maximum Current Burden <0.5VA
Maximum Voltage Burden <2VA for each line (Self Powered)
<0.1VA (Auxiliary powered)
Output Open Circuit Voltage <20V
Maximum Load 10V / Iomax
Max input for Max output 1.2√3VnIn

Accuracy

Class of Accuracy ±0.5%
Output Ripple < 0.5%
Range of Valid Accuracy 20% to 120% of Nominal input
0% to 120% of Nominal input (Auxiliary powered)

General

Case Polycarbonate
Fire Inflammable
Fixing Rail and Panel
Size 90*90*136 (mm)
Working Temperature 0 to 55°C
Storage Temperature -15 to 60°C
Response Time <300mSec
Isolation 2KV for 1 min.
Protection Degree IP-30

Standard Compliance

General IEC-688

Safety IEC-414, IEC-529

Auxiliary Supply

AC 100-120 Vac,±20%
DC 48 Vdc±20%


Active and Reactive Power Transducer

Voltage Transducer

Input-Output

Nom. Input Voltage (ph. to ph.)(Vn) 100V, 110V, 120V
Nom. Input Voltage (ph. to N)(Vn) 100/√3,110/√3,120/√3
Output Current Range (Iomin-Iomax) 0-1, 5, 10, 20mA, 4-20mA
Rated Frequency 45Hz - 55Hz
Overload Continues 1.2Vn
Overload for 10 Seconds 1.5Vn
Power Consumption <1.5VA
Maximum Burden <1.5VA (Self Powered)
<0.1VA (Auxiliary Supplied)
Output Open Circuit Voltage <20V
Maximum Load 10V / Iomax
Max input for Max output 1.2Vn

Accuracy

Class of Accuracy ±0.2%
Output Ripple < 0.2%
Range of Valid Accuracy 20% to 120% of Nominal input
0% to 120% of Nominal input (Auxiliary powered)

General

Case Polycarbonate
Fire Inflammable
Fixing Rail and Panel
Size 96*60*114 and 90*90*130 (mm)
Working Temperature 0 to 55°C
Storage Temperature -15 to 60°C
Response Time <300mSec
Isolation 2KV for 1 min.
Protect Degree IP-30

Standard Compliance

General IEC-688

Safety IEC-414, IEC-529

Auxiliary Supply

AC 100-120 Vac,±20%
DC 48 Vdc±20%


Voltage Transducer


Current Transducer

Input-Output

Nominal Input Current (In) 1A, 5A
Output Current Range (Iomin-Iomax) 0-1, 5, 10, 20mA, 4-20mA
Rated Frequency 45Hz - 55Hz
Overload Continues 1.5In
Overload for 1 Seconds 20In
Power Consumption <2VA
Maximum Burden <2VA (Self Powered)
<0.5VA (Auxiliary Supplied)
Max. Output Voltage <20V
Maximum Load 10V / Iomax
Max input for Max output 1.2In

Accuracy

Class of Accuracy ±0.2%
Output Ripple < 0.2%
Range of Valid Accuracy 10% to 120% of Nominal input
0% to 120% of Nominal input (Auxiliary powered)

General

Case Polycarbonate
Heat inflammable
Fixing Rail and Panel
Size 96*60*114 and 90*90*130 (mm)
Working Temperature 0 to 55°C
Storage Temperature -15 to 60°C
Isolation 2KV for 1 min.
Protection Degree IP-30

Standard Compliance

General IEC-688

Safety IEC-414, IEC529

Auxiliary Supply

AC 100-120 Vac,±20%
DC 48 Vdc±20%


MNC Current Transducer

Current Transducer


Resistor (Tap Position) Transducer

Input-Output

Nom. Input Resistance According to Order
Output Current Range (Iomin-Iomax) 4-20mA
Output Open Circuit Voltage <20V
Maximum Load 12V / Iomax

Accuracy

Class of Accuracy ±0.2%
Output Ripple <0.2%

General

Case Polycarbonate
Fixing Rail and Panel
Size 96*60*114 and 90*90*130 (mm)
Working Temperature 0 to 55°C
Storage Temperature -15 to 60°C
Response Time <300mSec
Isolation 2KV for 1 min.
Protection Degree IP-30

Standard Compliance

General IEC-688

Safety IEC-414, IEC-529

Auxiliary Supply

AC 100-120 Vac,±20%
DC 48 Vdc±20%


MNC Resistor (Tap Position) Transducer

Resistor (Tap Position) Transducer



MPR-G3

Paperless recorder
GENERAL SPECIFICATION:

  • Input signal: 4-20 mA
  • Number of channels: 6
  • Horizontal vertical bar & graph single channel & all channel display
  • Digital output and alarming capability
  • Channel to channel and bus isolation
  • Communication standard: IEC
  • Easy available & upgradeable
  • Daylight saving
  • Software based on industrial reliable multitask real time platforms
  • At least 0.3% accuracy of measurement
  • Natural cooling
  • Long life industrial LCD
  • More than one month storage capacity
  • Wide range power supply: 18-36 VDC
  • Menu driven user interface
  • Support of standard USB flash for data transfer & storage
  • Wide viewing angle
  • Self programming
  • Online history analyzing
  • Powerful analyzing tools
  • Direct excel file output
  • Setting based on password
  • Online system setting (no data lost)
  • Modular hardware setting
  • Hot plug in and out input modules
  • Self diagnosis & self checking